>>  Catalog Main : Power Products : PST

ONLINE CATALOG

PST-SB 250-650

Oil-Filled

Substation Class

pst_sb.gif (13028 bytes)

For a *.pdf of the current product catalog pages click HERE.

Application

Type PST transformers are designed to provide remote location station power needs up to 100 kVA as well as relaying performance or metering accuracy at 0.3% when loaded with IEEE burdens through ZZ. They are oil filled and hermetically sealed with a dry Nitrogen cushion.

Fabrication

Standard transformer tanks are manufactured from mild steel, protected with a zinc rich primer and acrylic top coat ANSI-70 gray paint suitable for withstanding the most rigorous environmental conditions. Porcelain clad bushings are one-piece wet process type designed to exceed IEEE standard creep and strike distances.

Magnetic circuits

All ITEC voltage transformers use high grade highly permeable silicon steel cores. Repeatability of accuracy performance from one transformer to another is dependent on consistent performance of quality core steel. For this reason all magnetic cores used in ITEC transformers are from high quality suppliers.

Primary terminals

Standard terminal for ITEC voltage PST model transformers is a four hole spade. Primary terminations are conveniently located at the top of the transformer for hook-up to high voltage lines.

Secondary terminals

Secondary terminations are brought into the low voltage compartment and secured to low voltage terminations for convenient connections. The low voltage compartment is suitably weatherproofed to maintain dry connections.

Drying and impregnation

In order to achieve the highest possible insulation integrity moisture content is minimized transformers are dried out and impregnated with transformer oil under vacuum in order to minimize moisture content. Dissipation factor readings are checked on each transformer at final test to insure proper drying has been achieved.

Testing

Every voltage transformer is tested in accordance with IEEE STD C57.13 (Latest revision). In addition ITEC tests each unit in accordance with NEMA 107. Extinction levels are required to be a minimum of 35% above operating voltage for all transformers.

Ground Connections

Each transformer is supplied with a NEMA 2-hole ground pad.

Nameplate Information

In addition to the nameplate, ratio information is stenciled onto the tank wall in 2" high numeric for remote identification.. OIL-23

 

 

Transformer Characteristics

 

Catalog ID

BIL

kV

Nom - System Voltage

Winding Ratio

Power Meter

Primary

Voltage

Power

Sec.Voltage

Sec.Voltage

25 kVA

50 kVA

100 kVA

One bushing for phase-to-ground application on three phase four wire GRD Y. Power windings only.

250

46000

110/221 N/A

27600

250/125

N/A

PA10250024025P0

PA10250024050P0

PA10250024099P0

350

69000

161/322 N/A

40250

250/125

N/A

PA10350035025P0

PA10350035050P0

PA10350035099P0

550

115000

276/522 N/A

69000

250/125

N/A

PA10550060025P0

PA10550060050P0

PA10550060099P0

650

138000

321/642 N/A

80500

250/125

N/A

PA10550070025P0

PA10650070050P0

PA10650070099P0

One bushing for phase-to-ground application on three phase four wire GRD Y. Power windings and meter winding Accuracy: 0.3@ W,X,Y,Z -ZZ Meter full winding thermal rating 6000 VA.

250

46000

110/221 & 240/400 :1

27600

250/125

115/69

PA10250024025M0

PA10250024050M0

PA10250024099M0

350

69000

161/322 & 350/600 :1

40250

250/125

115/67.08

PA10350035025M0

PA10350035050M0

PA10350035099M0

550

115000

276/522 & 600/1000 :1

69000

250/125

115/69

PA10550060025M0

PA10550060050M0

PA10550060099M0

650

138000

321/642 & 700/1200 :1

80500

250/125

115/67.08

PA10650070025M0

PA10650070050M0

PA10650070099M0

pst_sbdwg.gif (24130 bytes)

Specifications

Description

BIL

250

350

550

650

1. 1/2" drain valve.

8. Oil level indicator.

A

63"

71"

103"

107"

2. HO neutral bushing/removable ground strap.

9. Stainless steel nameplate.

B

36.5"

38.5"

40"

40"

3. HO bushing guard.

10. Mild steel tank.

C

28"

33"

56.5"

56.5"

4. Porcelain insulator, glaze ANSI 70

11. Lifting ears.

D

34"

36"

38"

38"

light gray.

12. Secondary terminal box w/3 each

E

23"

28"

45.5"

45.5"

5. Expansion chamber.

1 1/2" conduit knockouts.

Weight (lbs) Net

4200

4500

5000

5500

6. 3/4" NPT vacuum port-1/4" NPT pressure relief valve

13. 2-hole NEMA Standard ground pad.

Weight Ship 4700 5000 5500 6000

relief valve.

14. Baseplate with (4)

Oil Volume (gal)

95

130

170

175

7. Primary connection 4 -hole NEMA spade.

Mounting holes.

Min. Creep

37"

52"

101"

103"

   

Min. Strike

23.5"

25"

37.5"

41.5"

 

       >>  Catalog Main : Power Products : PST